Connect Modbus RTU Server Devices to a BACnet MS/TP System

Connect up to 32 Modbus RTU server devices to a BACnet MS/TP building automation system

460MMBMS

$896.72$979.31

SKU: 460MMBMS

INCLUDES
PRODUCT FEATURES
DATASHEETS & USERGUIDES

Connect Modbus RTU Servers to a BACnet MS/TP System

The 460MMBMS moves data between up to 32 Modbus RTU servers and a BACnet MS/TP BAS. It’s a perfect tool to tie Modbus power meters, boilers, chillers and other devices into your BACnet MS/TP Building Automation System.

Best of all the product is made in the USA, is always in stock and comes with a five-year warranty.

How Do I Use the 460MMBMS in My Application?

For most applications the mapping is very straight forward. Modbus register data is mapped to BACnet analog objects and Modbus coil data is mapped to binary objects on BACnet. The only additional piece required for BACnet is adding meta data which is nothing more than an ASCII description of each object. No other deep understanding of either protocol is required to configure the gateway.

It really is that simple. Need to modify your data as it passes from one protocol to the other? No problem. Each data mapping you apply can be modified with up to three mathematical functions. Add four to a value, multiply by four and divide by 10 with ease.

Move Your Data Bi-directionally

You can both send and receive data to and from your Modbus RTU server devices. Registers and coils in the Modbus RTU servers are mapped directly to BACnet MS/TP properties of Analog Input, Analog Output, Binary Input, and Binary Output. Up to 150 Analog Inputs, 150 Analog Outputs, 1600 Binary Inputs, and 1600 Binary Outputs can be mapped to registers and coils in up to 31 Modbus RTU server devices.

Why Use Real Time Automation as a Gateway Supplier?

The 460MMBMS provides an option to access Modbus RTU server devices on your BACnet MS/TP manager. While there are certainly a number of other companies offering stand alone gateways, there is no one who provides the level of support and service that you receive from RTA.

When you call, a live person answers the phone. When you talk with sales, you will get honest answers and recommendations even if that means recommending someone else’s solution. When you get support, it is from an engineer who had a hand in the product’s development, and support doesn’t require a ticket or 24 hour wait.We are unashamed of the fact that we are a smaller company because that means you mean a lot more to us.

Modbus RTU Master Features

Modbus Operation Modes: Modbus RTU Master
Function Codes Supported: 1, 2, 3, 4, 5, 6, 15 & 16
Swapping: Byte and Word Swapping
Maximum Modbus RTU Slave Devices: 32
Number Read/Write Scan Lines per RTU Slave Device: 200 Total - 100 reads & 100 writes
Scan Line Support: Up to 125 Registers or 512 Coils

BACnet MS/TP Slave Features

BACnet/ MS/TP Operation Modes: BACnet MS/TP Master Responder
Supported Object Types: Device, Binary I/O, Analog I/O, Character String Value
Supported Service Codes: Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, Device Dynamic Binding, Dynamic Object Binding-B, Device Communication Control-B
Maximum Connections: 1
Analog Objects: Supported 1200 Input and 1200 Output
Binary Objects: Supported 1600 Input and 1600 Output