Ethernet TCP/IP to DH+ Device

Join your Ethernet TCP/IP via a socket connection to a DH+ device. Now you can link up to 10 Ethernet TCP/IP devices with as many as 32 DH+ devices. It’s perfect for many legacy manufacturing applications.

460TCPDHM

$1,495.00$1,510.75

SKU: 460TCPDHM

INCLUDES
PRODUCT FEATURES
DATASHEETS & USERGUIDES

Map Your Legacy PLC to a TCP/IP Socket

You can now make your legacy serial PLCs look like Ethernet TCP/IP data! Connect your Ethernet TCP/IP to a DH+ device. Any of your old serial PLCs like the PLC5 or SLC can now provide data to Ethernet TCP/IP applications. It’s the perfect tool to keep those old legacy PLCs from the scrap pile.

How Do I Use the 460TCPDHM-D2E in My Application?

When you connect your Ethernet TCP/IP to DH+ device it parses incoming and outgoing ASCII data from TCP/IP packets into data segments and assigns it a data type. It then maps those values to matching file locations in the DH+ devices like N7:200 or F9:1, the whole process is simplified for you.

What Is DH+ and What It Can Do for You?

Discover whether a DH+ device aligns with your specific needs. Check out our DH+ tech page — DH+ introduces a token-passing type network where each node receives the token and can transmit messages only when holding it.

Why Use Real Time Automation as a Gateway Supplier?

While there are certainly other companies offering protocol gateways, there is no one who provides the level of support and service that you receive from Real Time Automation. When you call us, a live person answers the phone. If you talk with our sales team, you will get honest answers and recommendations. And rest assured, all the support you get is from an engineer who had a hand in the product’s development, and support doesn’t need a ticket or 24-hour wait. We get back to you as soon as possible. It’s an RTA promise.

DH+ Features

Operation Mode: DH+ Master
PLCs Supported: 5/04, PLC5
Maximum Devices Supported: 32
Scan Lines: 100 input / 100 output
Supported Data Types: 100 Integers or 100 Binaries, or 50 floats, 82 character string per Scan line

Ethernet TCP/IP Device Features

Operation Modes: Client or Server
Maximum Number of Devices Supported: 10
Maximum Number of Characters Transferred: 1024
Delimiter Processing: Incoming Delimiters automatically removed; Outgoing Delimiters automatically added
Parsing: Parse String of ASCII Data in up to 50 Segments by Delimiter or Offset
Concatenation: Concatenate up to 50 segments/strings of ASCII data with optional delimiter