Connect EtherNet/IP to BACnet MS/TP Master

Connects up to 32 EtherNet/IP Adapters with a BACNet MS/TP Master

SKU: 460ECBMS

460ECBMS

Price$805.00$976.25

Clear

Product Description

Connect EtherNet/IP Adapter Devices to a BACnet MS/TP Master
The 460ECBMS moves data between a BACnet MS/TP Master device and an EtherNet/IP network of up to 32 Adapter devices. It’s the perfect tool to tie all of your EtherNet/IP devices into your BACnet MS/TP Building Automation System. Bridge your factory automation systems with your building automation systems.

How Do I Use 460ECBMS-N34 in My Application?
Up to 496 bytes of data from your EtherNet/IP Adapters will be mapped into your BACnet MS/TP Master as BACnet MS/TP data. When writing from your BACnet MS/TP Master to your EtherNet/IP Adapters, up to 496 bytes of BACnet MS/TP data will be mapped to up to 32 EtherNet/IP Adapters as EtherNet/IP data.

It’s really that simple. Need to modify your data as it passes from one protocol to the other? No problem. Each data mapping you apply can be modified with up to 3 mathematic functions. Add 4 to a value, multiply by 4 and divide by 10 with ease.

Why Use Real Time Automation as a Gateway Supplier?
While there are certainly other companies offering protocol gateways, there is no one who provides the level of support and service that you receive from RTA.

When you call, a live person answers the phone. When you talk with sales, you will get honest answers and recommendations. When you get support, it is from an engineer who had a hand in the product’s development, and support doesn’t require a ticket or 24-hour wait.

Try the RTA difference today.

  • Manual
  • 3’ power cable with Flying leads
  • 5 Year Hardware Warranty
  • IPSetup software — Automatically locates RTA Gateway on the network
  • Unlimited Firmware Feature Upgrades for Life
  • CAT5 Cross over cable for direct connection to PC during programming
  • Complete, Unlimited Access to our Industry Leading Support Staff

Ethernet/IP Scanner Features

Operation Modes
Class 1 I/O Scanner (minimal Adapter is required and supported)

Message Support
Implicit Class 1 Cyclic I/O, Explicit not supported.

Data Types
BIT8,16 & 32; INT8, 16, 32 & 64; UINT8,16, 32 & 64; Float & Double

Maximum EtherNet/IP Adapter Devices
32

Max Data Per Adapter Connection
Up to 496 bytes in each direction

BACnet MS/TP Slave Features

BACnet/ MS/TP Operation Modes
BACnet MS/TP Master Responder

Supported Object Types
Device, Binary I/O, Analog I/O, Character String Value

Supported Service Codes
Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, Device Dynamic Binding, Dynamic Object Binding-B, Device Communication Control-B

Maximum Connections
1

Analog Objects
Supported 1200 Input and 1200 Output

Binary Objects
Supported 1600 Input and 1600 Output

Gateway Security

You can configure up to 9 different users access to diagnostic and configuration screens.

Alarming

Set <, <=, >=, >, ==, !=, and Change-of-State rules on any data moving through the gateway. If alarm rule is triggered an email notification can be sent.

Translation Table

Allows for data manipulation during protocol translation. Scaling and other data format changes can occur in the gateway.

Status and Counters

Protocol specific status, counters and error messages are accessible within the gateways diagnostics page. They can also be delivered to a connected device.

Diagnostic Logging Page

Allows users to see and log start up sequences, protocol specific messages & error messages.

 

460ECBMS-N2EW
DATASHEET  USERGUIDE
460ECBMS-N2E
DATASHEET  USERGUIDE
460ECBMS-N34
DATASHEET  USERGUIDE
460ECBMS-N700
DATASHEET  USERGUIDE
460ECBMS-NNA1
DATASHEET  USERGUIDE
460ECBMS-NNA4
DATASHEET  USERGUIDE