Modbus TCP Client to BACnet/IP Client Protocol Gateway
The easiest way to integrate Modbus TCP Clients with a BACnet/IP building automation system. The 460MSBS gateway allows you to move automation data between up to 10 Modbus TCP client and a BACnet/IP-controlled building automation system (BAS) or controller.
460MSBS
Price range: $896.72 through $1,035.00
Connect Your Modbus TCP Network to Your Modern Building Management System

The 460MSBS moves automation data between up to 10 Modbus TCP clients and a BACnet/IP building automation system (BAS) or controller. It’s a perfect tool to integrate modern Modbus-based controllers and PLCs into your BACnet/IP architecture.
How Does the 460MSBS Protocol Gateway Move Data in My Application?
For most applications, the data mapping is very straight forward:
- Modbus register data is mapped to BACnet Analog Inputs (AI) and Analog outputs (AO)
- Modbus coil data is mapped to BACnet Binary Inputs (BI) and Binary Outputs (BO)
The only additional piece of information required for BACnet is adding metadata, which is nothing more than an ASCII description of each object. No other deep understanding of either protocol is required to configure the gateway. It really is that simple.
Need to modify your data as it passes from one protocol to the other? No problem. Each data mapping you apply can be modified with up to three mathematical functions. This allows you to manipulate values within the gateway itself before data reaches its destination.
Not exactly what you were looking for? Real Time Automation offers a full line of Modbus TCP protocol gateways and BACnet/IP protocol gateways.
Simplify Device Connectivity with Modbus Device Templates
Configuring your RTA Modbus TCP Client to BACnet/IP Client protocol gateway is as easy as loading a file!
Real Time Automation provides over 400 pre-defined Modbus device profiles from over 70 vendors. All you need to do is assign the IP and serial network settings, upload the template file and the gateway automatically populates the entire Modbus data point list and sets up the corresponding BACnet points. It’s that easy!
- No manual entry of Modbus registers or data mapping to BACnet objects
- Customizable tag names to fit your existing naming conventions
Why Trust Real Time Automation As Your Protocol Partner?
While there are certainly other companies offering protocol gateways, no one provides the level of support and service that you receive from Real Time Automation.
- Total protocol lifecycle support
- Talk to a live person from our Wisconsin-based headquarters every time you call
- Receive honest answers and recommendations from our sales team
- Get live Enginerd support that provides timely issue resolution without opening tickets or 24-hour wait times
460MSBS Frequently Asked Questions
The 460MSBS is available in a variety of platform options to meet your unique application needs. Use the platform comparison table to determine the right platform for you.
Purchases can be made through authorized RTA distributors or directly from Real Time Automation. Orders may be submitted by emailing a purchase order to orders@rtautomation.com or by purchasing directly on the RTA website with a credit card.
The 460MSBS is delivered with a 5-year warranty.
RTA offers multiple support options. Live Enginerd support is available from 8am to 5pm CST. Call 800-249-1612, email support@rtautomation.com or visit the support page.
Modbus TCP/IP Server Features
Modbus Operation Modes: Modbus TCP/IP ServerFunction Codes Supported: 1, 2, 3, 4, 5, 6, 7, 15 & 16
Swapping: Byte and Word Swapping
Maximum Modbus TCP/IP Client Connections: 10
Contiguous Data Areas: 200 Total - 100 reads & 100 writes
Data Area Limits: 500 Contiguous Coils or 500 Contiguous Registers
BACnet/IP Server Features
BACnet/IP Operation Modes: BACnet/IP ServerSupported Object Types: Device, Binary I/O, Analog I/O, Character String Value
Supported Service Codes: Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, Device Dynamic Binding, Dynamic Object Binding-B, Device Communication Control-B
Maximum Connections: 1
Analog Objects Supported: 1200 Input and 1200 Output
Binary Objects Supported: 1600 Input and 1600 Output